WAC 296-104-301
Installation -- What control and limit
devices are required on automatically fired boilers after June
1989? In addition to those requirements listed in WAC 296-104-300, the following are also required:
(1) All boilers that are automatically fired low pressure
steam heating boilers, small power boilers, and power steam
boilers without a constant attendant who has no other duties
shall be equipped with:
(a) Two high steam pressure limit controls, the highest
of which shall be provided with a manual reset.
(b) Two low-water fuel cutoffs, one of which shall be
provided with a manual reset device and independent of the
feed water controller.
(c) Coil type flash steam boilers may use two
high-temperature limit controls, one of which shall have a
manual reset. This is instead of the low-water fuel cutoff.
(d) All control and limit devices shall be independently
connected and electrically wired in series.
(2) All automatically fired hot water supply,
low-pressure hot water heating boilers, and power hot water
boilers shall be equipped with:
(a) Two high-temperature limit controls, the highest of
which shall be provided with a manual reset.
(b) One low-water fuel cutoff with a manual reset and
independent of the feed water controller.
(c) For coil type hot water boilers a low-water flow
limit control installed in the circulating water line may be
used instead of a low-water fuel cutoff.
(d) All control and limit devices shall be independently
connected and electrically wired in series.
[Statutory Authority: Chapter 70.79 RCW. 04-21-069, §
296-104-301, filed 10/19/04, effective 1/1/05.]