WAC 296-150F-0320
What must I provide with my request
for design-plan approval by the department? All requests for
design-plan approval must include:
(1) A completed design-plan approval request form;
(2) Two complete sets of design plans,
specifications, engineering analysis, test procedures and
results plus one additional set for each manufacturing
location where the design plan will be used (see WAC 296-150F-0340 and 296-150F-0350);
(3) At least one set of design plans must have an
original wet stamp from a professional engineer or architect
licensed in Washington state. All new, renewed, and
resubmitted plans, specifications, reports and structural
calculations prepared by or prepared under his or her direct
supervision shall be signed, dated and stamped with their
seal. Specifications, reports, and structural calculations
may be stamped only on the first sheet, provided this first
sheet identifies all of the sheets that follow are included
and identified in the same manner. Plans that have not been
prepared by or under the engineer's or architect's supervision
shall be reviewed by them and they shall prepare a report
concerning the plans reviewed. This report shall:
(a) Identify which drawings have been reviewed by drawing
number and date;
(b) Include a statement that the plans are in compliance
with current Washington state regulations; and
(c) The report shall be stamped and signed by the
reviewer.
Any deficiencies shall be corrected on the drawings
before submitting to the department or be included in the
report and identify as to how they are to be corrected. This
report shall be attached to the plan(s) that were reviewed.
We will retain the set with the original wet stamp;
(4) A one-time initial filing fee and the design-plan fee
(see WAC 296-150F-3000); and
(5) A "key drawing" to show the arrangement of modules if
the plan covers three or more modules.
(6) Electrical plan review for educational, institutional
or health care facilities and other buildings. Plan review is
a part of the electrical inspection process; its primary
purpose is to determine:
(a) That loads and service/feeder conductors are
calculated and sized according to the proper NEC or
WAC article or section;
(b) The classification of hazardous locations; and
(c) The proper design of emergency and standby systems.
(7) All electrical plans for new or altered electrical
installations in educational, institutional, and health or
personal care occupancies classified or defined in this
chapter must be reviewed and approved before the electrical
installation or alteration is started. Approved plans must be
available for use during the electrical installation or
alteration and for use by the electrical inspector.
(8) All electrical plans for educational facilities,
hospitals and nursing homes must be prepared by, or under the
direction of, a consulting engineer registered under chapter 18.43 RCW in compliance with chapters246-320, 180-29, and 388-97 WAC as applicable and stamped with the engineer's mark
and signature.
(9) Plans to be reviewed by the department must be
legible, identify the name and classification of the facility,
clearly indicate the scope and nature of the installation and
the person or firm responsible for the electrical plans. The
plans must clearly show the electrical installation or
alteration in floor plan view, include switchboard and/or
panel board schedules and when a service or feeder is to be
installed or altered, must include a riser diagram, load
calculation, fault current calculation and interrupting rating
of equipment. Where existing electrical systems are to supply
additional loads, the plans must include documentation that
proves adequate capacity and ratings. The plans must be
submitted with a plan review submittal form available from the
department.
[Statutory Authority: Chapter 43.22 RCW. 07-05-063, §
296-150F-0320, filed 2/20/07, effective 4/1/07; 05-23-002, §
296-150F-0320, filed 11/3/05, effective 12/4/05. Statutory
Authority: RCW 43.22.340 and 43.22.480. 99-13-010, §
296-150F-0320, filed 6/4/99, effective 7/5/99. Statutory
Authority: RCW 43.22.340, [43.22.]355, [43.22.]360,[43.22.]432
, [43.22.]440 and [43.22.]480. 96-21-146, §
296-150F-0320, filed 10/23/96, effective 11/25/96.]