| Exemption: |
• You are exempt from the requirement not to install the shut off valve between the safety relief valve and the
container or systems in the following situations: |
|
– A three-way valve installed under two safety relief valves, each with |
|
▪ The required rate of discharge; |
|
AND |
|
▪ Installed to allow either of the safety relief valves to be closed off but not at the same time. |
|
– Two separate relief valves are installed with individual shut off valves. |
|
▪ The two shut off valve stems must be mechanically interconnected to allow the full required flow of one
safety relief valve at all times. |
|
– When a safety relief valve manifold that allows: |
|
▪ One valve of two or more to be closed off; |
|
AND |
|
▪ The remaining valve or valves will provide not less than the rate of discharge shown on the manifold
nameplate. |
| If you have: |
Then make sure they: |
| Columnar-type
gauges |
Are restricted to stationary storage
installations |
|
Are shielded against the direct rays
of the sun |
|
Are equipped with all of the
following: |
|
• |
Shut off valves having
metallic hand-wheels |
|
• |
Excess flow valves |
| |
• |
Extra heavy glass that is
adequately protected with a
metal housing applied by the
gauge manufacturer |
| Main shut off
valves |
Are kept closed and locked when the
installation is unattended |
| |
Exemption: Valve locks are not
required if the facility is protected
against tampering by fencing or
other suitable means. |
| Filling
connections |
Are provided with one of the
following: |
|
• |
Combination back-pressure
check valve and excess flow
valve |
|
• |
One double or two single
back-pressure check valves |
| |
• |
A positive shut off valve in
conjunction with either an
internal back-pressure check
valve or an internal excess
flow valve |
| Underground
installations with
a probability of
the manhole or
housing
becoming
flooded |
Have vent lines located above the
high water level |
|
Have manholes or housings with
ventilated louvers or their equivalent
with the area of their openings equal
or exceeding: |
| |
• |
The combined discharge areas
of the safety relief valves and
vent lines which discharge
their content into the manhole
housing |
| Hydrostatic
relief valves |
Are installed between each pair of
valves in the liquid ammonia piping
or hose. |